5 technical data for 3-wire transmitter, Outp ut supply ambient conditions – JUMO 707030 dTRANS T03 2-Wire/3-Wire Transmitter Operating Manual Benutzerhandbuch
Seite 84

40
5 Technical data for 3-wire transmitter
Outp
ut
Supply
Ambient conditions
Output signal
DC curr
ent 0
—
10
V
T
ransfer characteristic
linear with temperatur
e
T
ransfer accuracy
± 0.2
%
a
a
All ac
curacies given in % r
e
fer to the ra
ng
e-end va
lue 10
V
D
a
mping o
f ripple
on supply voltage
>
40
dB
Load
10
k
Load err
o
r
± 0.1
%
Settling time on a
temperatur
e chan
ge
10
msec
Calibration con
d
itions
24
V
D
C at appr
ox. 22
°C
Calibration/con
figuration accuracy
± 0.2
%
or
± 0.2
°C
b
The lar
g
er value applies.
c
If the measur
ing range
end valu
e >
600
°C then
the c
a
libration or c
o
nfig
ura
tion ac
curacy is
± 0.4
%
S
u
pp
ly voltag
e (Ub)
15
—
3
0
V
DC
Reverse polarity pr
otection
yes
S
u
pp
ly voltag
e er
ro
r
± 0.01
% per V deviation fr
om 24
V
a
a
All ac
curacies given in % r
e
fer to the ra
ng
e-end va
lue 10
V
dTRANS T03 BU
T
y
pe 707033/...
dTRANS T03 TU
T
y
pe 707034/...
Operating temperatur
e
range
-40
to
+85
°C
-25
to
+70
°C
Storage temperatur
e range
-40
to
+85
°C
T
e
mperatur
e err
o
r
± 0.01
% per °C deviation fr
om 22
°C
a
Climatic conditions
re
l. humidity
95
% annual mean, no condensation