Baumer BA DABU MP4M Benutzerhandbuch
Seite 12

DABx_MP4M_BA_V2_3m.doc
23/28
Baumer Electric AG
19.12.07/rut
Frauenfeld, Switzerland
4.9 Limit switches with switching output
Two independent working limit switches can be adjusted on this device.
4.9.1
Limit switches representation in % of output
Voltage output
Current output
actual measuring value
SIG 6.05V
30.4% 50.4%
Limit switch 1
Limit switch 2
actual measuring value
SIG 6.05mA
30.4% 50.4%
Limit switch 1
Limit switch 2
Example:
Limit switch 1 (30.4 %) = 3,04 V
Limit switch 2 (50.4 %) = 5,04 V
Example:
Limit switch 1 (30.4%) = 8.864 mA
Limit switch 2 (50.4%) = 12.064 mA
[4 mA + (16 mA x 50.4 x 0,01) = 12.064 mA]
4.9.2
Procedure of limit switch storage
0.1. External DIP switch has to stay on
OFFPress rotary button briefly
*
Limit switch 1 flashes on the display
1.
Press rotary button briefly
*
Limit switch 1 flashes on the display
2.
Change limit switch 1
Turn rotary button
3a. Press rotary button briefly
Limit switch 2 flashes on the display
3b. Press rotary button more than 3 seconds
“SAVE” is indicated on the lower display during
2 seconds
4.
Change limit switch 2
Turn rotary button
5a. Press rotary button briefly
Limit switches are not stored
5b. Press rotary button more than 3 seconds
“SAVE” is indicated on the lower display during
2 seconds
If there is no action during 10 seconds (turn or press rotary button) the program will determine
automatically the adjusting mode and return to the active mode. The changed limit switches will be
put back to the original values.
DABx_MP4M_BA_V2_3m.doc
24/28
Baumer Electric AG
19.12.07/rut
Frauenfeld, Switzerland
4.9.3
Example of function and wiring of switching output
Example of function
Signal
Limit switch 1
Limit 1
Limit 2
High
High
Low
Low
Limit switch 2
Wiring
+Vs
6
7
Switch1
Switch2
3, 5, 9 GND
I
L
< 50mA