3.3 Assignment signal input
Choice of PNP or NPN The contacts 9 to 12 are comparator signal inputs.
They can be triggered either by PNP or NPN encoders. The input
logic as well as the operating threshold are correspondingly chosen
in programming line 28. The contacts 9 (Track A) and 10 (Track B) are
counting inputs for a counting range between 3 Hz, 25 Hz or 10 kHz.
The counting rate is determined in programming lines 26 and 27.
The contacts 11 and 12 are 2 control inputs for Reset, Stop, Hold,
Print, Keylock, etc. The function of these control inputs is selected in
the programming lines 29 and 31
Input resistance
Selectable operating threshold
approx. 3 kΩ
2.5 V, 5 V and 10 V
3.4 Typical connections
Sensor
Assignment
Programming
Contact
Counting rate:
9 track A
Line 26 to 1 = 25 Hz
8 +24 V
Line 26 to 2 = 3 Hz
Proximity switch PNP or NPN
9 track A
Input logic:
8 +24 V
Line 28 to 0 = PNP
7 0 V
Line 28 to 1 = NPN
Namur without explosion protection
9 track A
Input logic:
7 0 V
Line 28 to 3 = NPN
Incremental
Counting mode:
9 track A
A 90º B (x1, x2, x4)
10 track B
Line 25 to 3, 4, 5
8 +24 V
Counting rate:
7 0 V
Line 26, 27 to
0 = 10 kHz