Process Diagram: Automated Conveyance (1)

Lock OFF, conveying valve CLOSED,
Sealing air CLOSED

Basic function

operations OFF

kv_max value known

QL(p) known

No alarm

Selection of conveying recipe

Main pressure present

Data entry manual or by means

of binary inputs C10, C12:

- START

- STOP

- ALARM RESET

Binary input C11:

- Empty run

Output transmitter signal

from conveying pressure p

on a cyclical basis as

monitor signal to port B6

AND

Start

Sealing air valve open

Start up conveying valve

(target value vE by ramping with

ramp time tvE,

calculation not including leakage)

Time t1 = 15 s

(adjustable 1...100 s)

Lock IN

Q0 = Qeff + QL(p)

Adjust conveying valve

1

4

START:
*C10 (Start/Stop)=1 OR
*C13 (Key-operated switch)=1 AND
SELECT key

Conveying valve opening in % according to
4040 stipulations and setting of
positioner

t1 from recipe;
Settling time after start

Compensation for lock leakage
(Qeff=amount over line length)

Monitor main pressure p1

and PIA02 on a cyclical basis

when conveying has started

p1 < 0.2 bar OR

PIA02 =1

ALARM 5

Adjust conveying valve to

empty- run target value

vL [m/s; target figure by

ramping with ramp time

tvL=30 s;

Calculation including

leakage

C11 (empty run) =1?

j

j

O

PERATION