Burkert Type 4040 Benutzerhandbuch

Seite 9

Advertising
background image

4040 - 7

english

0

0

5

3

10

6

100 100

S

TARTUP

Entering the support points:

back to
CHARACT

Valve lift [%] (Entry using arrow keys)

Target control value [%]
(Support point)

Type 2712 DN40-Seat Ø40

Type 2712 DN40-Seat Ø32

Target value

Lift

Target value

Lift

0

0

0

0

5

21

5

25

10

38

10

39

15

47

15

48

20

54

20

57

25

60

25

63

30

65

30

67

35

68

35

70

40

71

40

73

45

74

45

75

50

76

50

78

55

79

55

80

60

81

60

83

65

84

65

86

70

87

70

88

75

89

75

90

80

92

80

92

85

94

85

94

90

96

90

96

95

98

95

98

100

100

100

100

During conveyance, a part of the air is lost in the lock. As the device is only able to record the amount of air
before the lock, a leakage characteristic must first be read in. In order to determine the amount of leakage air,
which depends on the conveying pressure, the valve is slowly opened from 0 to 100% in 30 seconds, and the
leakage value is stored in intervals of 0.5 bar. During this process, each recorded value appears for 1 second
on the display.

The function "Read in Leakage Air" can be called up using the configuration menu and selecting "Valve Cha-
racteristic".

CAUTION

Be sure to observe the directions regarding the state of the system in the process
plan "Read in Leakage Air".

CAUTION

Be sure to observe all starting conditions for conveyance. They can be found in the
process plan "Automated Conveyance".

Read in leakage characteristic

After these startup steps have been carried out, the device is ready for operation.