Operation with the regulator Type 4040 requires a control valve with a linear flow characteristic. As Bürkert's
control valve Type 2712 does not have a linear characteristic, but a percentually equal one, the linearization
must be carried out using the positioner TopControl Type 8630 or the SideControl Type 8635.

The procedure is as follows:
First the additional function CHARACT must be activated. A freely programmable characteristic can be defi-
ned using the menu selection CHA FREE. The support points must be entered in increments of 5%, and can
be obtained from Bürkert representatives for the control valve Type 2712.

CHARACT

Selection of the transmission characteristic between input signal (target control value) and lift (cor-
rection characteristic)

Customer-specific characteristic

Setting: CHA LIN

Using this additional function, you can select a transmission characteristic for the target value (target posi-
tion, CMD) and valve lift (POS) in order to correct the flow / operative characteristic.

Linear characteristic

Percentually equal characteristic 1 : 25

Percentually equal characteristic 1 : 33

Percentually equal characteristic 1 : 50

Inverse percentually equal char. 25 : 1

Inverse percentually equal char. 33 : 1

Inverse percentually equal char. 50 : 1

User-defined cha-
racteristic, pro-
grammable using
support points

Values according to table

Correction of Characteristics for the Operation with Control Unit, Type 4040