page / Seite 12/83

3.4 Technical

data

Housing material:

Aluminium sheet, sheet steel, galvanized
and coated

Operating Temperature range:

10 °C to 35 °C / 50°F to 95°F


abs. atmospheric humidity:

8g / kg maximum


Air outlet to heat exchanger:

20 to 25°C / 68 to 77°F according to ASHRAE


Temperature difference across server:

approx. 15K


Noise level:

55 dB(A) sound pressure at a distance

of 1 m


Useful

load

1.000

kg

/

2204

pounds

Chilled water
Effective cooling capacity
depending on type:

12 KW to 25 / 35)* KW


Feed temperature:

12°C / 54°F (other temp. upon consultation)


Return temperature:

18°C / 64°F
)*21°C/ 69,8°F at 35 kW (Blade application)
(other temp. upon consultation)

Max. operating pressure:

10 bar / 145 PSI


Feed/return supply connection:

1“