The programming of the control is factory preset and password protected.
The failure of the temperature sensor or one of the fans set an alarm using a potential free contact.
Following alarms can be also provided to potential free contacts:
- sensor
error
- fan
malfunction
-
high temperature (two levels)
The fans are automatically shut down if the server cabinet rear door is opened.
fan control characteristic (factory setting)
Start at 20°C
valve actuator
Three way valve
Bypass
(flow direction)