Cooltherm, Storage and transportation – Liebert Rack Enclosure With Integrated Liquid Cooling XDK-W Benutzerhandbuch
Seite 19

CoolTherm
Manual / Bedienungsanleitung
CoolTherm
01_998_330_0_k
page / Seite 17/83
three- way valve control characteristic (factory setting)
4.
Storage and transportation
•
Cover open pallets with tarpaulins and protect the components
from soiling (e. g. sand, rain, dust, etc.).
•
Keep storage temperatures between –30 °C and +50 °C / -22°F and 104°F.
•
The heat exchanger must be completely drained (to prevent the risk of
frost damage)
•
When stored for more than 1 year, check the the fan bearings prior to
installation. (
⇒ Turn fans by hand.)
•
CoolTherm can be transported using a forklift truck or crane. For transport
using a crane, straps must be used. The CoolTherm weighs, depending on
the version, up to 340 kg / 749 lbs. (net weight)
•
Avoid twisting the housing or other damage.
•
Use suitable tools during installation, e. g. approved scaffolding.
•
Prior to lifting the CoolTherm using a crane or forklift truck, close all doors.
•
Do not stand under suspended loads.
•
Hooks attached to the load must be be of appropriate tensile strength.
•
CoolTherm must not be lifted at an angle using a crane.
•
All packaging is to be removed prior to commissioning CoolTherm.
Start at 16°C
air inlet