Data overview CoolTherm Table B (Hydraulic Data)
effective
cooling
capacity
total cooling
capacity
(at normal
operation)
total cooling
capacity
(at full speed
operation /
emergency)
water
content
water flow
rate
pressure
loss
cabinet
water
temperature
rise
(at normal
operation)
water
temperature
rise
(at full speed
operation /
emergency)
kw
kw kw l
m³/h
bar
K K
12
12,5 13,0 5,9
1,79
0,41 6 6,2
17
17,8 18,4 7,9
2,55
0,62
6 6,2
25
26 26,8 9,9
3,72
0,58
6 6,2
35
36 36,8 9,9
3,72
0,58
8,1
8,51