Cooltherm, Server, Description 3.1 general function – Liebert Rack Enclosure With Integrated Liquid Cooling XDK-W Benutzerhandbuch

Seite 8

Advertising
background image

CoolTherm

Manual / Bedienungsanleitung

CoolTherm 01_998_330_0_k

page

/

Seite

6/83

Temperature

spread,

water:

6K


Use of anti-freeze in the chilled water: upon

request


Water

connection:

from

below


Condensed water connection:

from below

Nominal voltage at cooling capacity:

12 KW, 17 KW, 25 KW

200V to 264V /

50Hz / 60 Hz


Max. operating pressure:

10 bar / 145 PSI



3. Description
3.1 General

function

CoolTherm complies with the conditions of EN 60950
The modular design facilitates the installation of all 19“ equipment of varying depth.
Heat produced by installed equipment (e. g. servers) is reliably removed using the cold water
system integrated into the server cabinet. The cooling system is inherently safe because water
cannot reach the server area.
The cooling system comprises a high-performance air/water heat exchanger, fans with fan control
unit (fan-speed according to heat load) for the ducted supply of air and cold water connection.
The air circuit is closed such that no heat (thermal load) is emitted to the environment.




Attention!

CoolTherm

only

works if cold server feed air

and heated server outlet air are fully separated.

Height units not in use have to be sealed using blanking panels.

























Server

Luftkanal

Lufttrennung

KALT

KALT

WA

R

M

WA

R

M

WA
R

M

WA
R

M

WARM

WARM

WARM

WARM

COLD

Air duct

Air separation

Top view