Cooltherm, 3 chilled water connection – Liebert Rack Enclosure With Integrated Liquid Cooling XDK-W Benutzerhandbuch

Seite 23

Advertising
background image

CoolTherm

Manual / Bedienungsanleitung

CoolTherm

01_998_330_0_k

page / Seite 21/83

Remove both screws



5.3 Chilled

water connection


The heat exchanger can be pulled out for servicing
Chilled water pipes should be connected so that the heat exchanger
can be pulled out when the connection is undone.
If the heat exchanger is connected to the chilled water network using threaded fittings,
the pipe fitting must be supported on tightening.
Prior to commissioning the server cabinet, the pipe connections
should be checked for leaks.


Preparing heat exchanger for initial commissioning:

-

Check the mechanical installation and the supply pipe connection.



Remove this air duct for
bleeding, draining the
heat exchanger and
checking the valve