WIKA operating instructions attachable indicator model A-AI-1

16

2018357.06 08/2012 GB/D

Parameters of the A-AI-1 attachable indicator

Parameters Values

Description

Key 1

Keys 2 and 3

dP

Position of the decimal point (decimal point)

----

Max. indication range: -1999 … 9999

---.-

Max. indication range: -199.9 … 999.9

--.--

Max. indication range: -19.99 … 99.99

-.---

Max. indication range: -1.999 … 9.999

di.Lo

Lower indication range limit (display low)

-1999 ... 9999 This value will be displayed when the input signal

= 4 mA

di.Hi

Upper indication range limit (display high)

-1999 ... 9999 This value will be displayed when the input signal

= 20 mA

Li

Measuring range limit (limit)

oFF

deactivated

Exceeding the measuring range limits is permitted

up to the measuring limit (see note)

on.Er

active, (error display):

The measuring range is limited exactly to the input

signal. When this exceeds or drops below it, a

corresponding error message is displayed.

on.rG

active, (display measuring range limits):

The measuring range is limited exactly to the input

signal. When this exceeds or drops below it, the

indication range limit is displayed. (e.g. for a humid-

ity of 0 ... 100 % r.H: by dropping below the limit 0 is

displayed, and by exceeding it 100 is displayed.

When the measuring limits are exceeded (at either end), independ-

ently of the limit settings, the corresponding error message

appears ("Err.1" or "Err.2"). The measuring limits are between

approx. 3.7 and 20.8 mA.

FiLt

Filter (filter)

oFF

Filter deactivated

0.1 ... 2.0

Activate the filter in order to prevent the display

from 'jumping' with every small fluctuation and to

suppress single spikes. The larger the number, the

stronger the filtering.