8. Faults

8. Faults

If the instrument detects any fault conditions, the corresponding error code

will be displayed.

The following error codes are defined:

Error

Causes

Measures

Err.1

Measuring range

exceeded

■

Input signal too high

■

Faulty connection

■

The error message will reset

itself once the input signal is

once more within the permis-

sible limits.

■

Check the transmitter and

the instrument configuration

(e.g. input signal).

Err.2

Measured value

below allowable

range

■

Input signal too low, or

negative

■

Current less than 4 mA

■

Sensor burnout

■

The error message will reset

itself once the input signal is

once more within the permis-

sible limits.

■

Check the transmitter and

the instrument configuration

(e.g. input signal).

Err.3

Indication range

exceeded

■

Scaling incorrect

■

The error message will be

reset once the display value

is once more < 9999.

Err.4

Under the indica-

tion range

■

Scaling incorrect

■

The error message will reset

itself once the display value

is once more within the

permissible limits.

Err.7

System error

■

Permissible operating

temperature too high or

too low.

■

Instrument faulty

■

Abide by the operating

temperature limits

■

Replace instrument

Err.11

Value could not be

calculated

■

Scaling incorrect

■

Check the setting and the

input signal