8. Faults

8. Faults

If the instrument detects any fault conditions, the corresponding error code

will be displayed.

The following error codes are defined:

Error

Causes

Measures

Err.1

Measuring range

exceeded

Input signal too high

Faulty connection

The error message will reset

itself once the input signal is

once more within the permis-

sible limits.

Check the transmitter and

the instrument configuration

(e.g. input signal).

Err.2

Measured value

below allowable

range

Input signal too low, or

negative

Current less than 4 mA

Sensor burnout

The error message will reset

itself once the input signal is

once more within the permis-

sible limits.

Check the transmitter and

the instrument configuration

(e.g. input signal).

Err.3

Indication range

exceeded

Scaling incorrect

The error message will be

reset once the display value

is once more < 9999.

Err.4

Under the indica-

tion range

Scaling incorrect

The error message will reset

itself once the display value

is once more within the

permissible limits.

Err.7

System error

Permissible operating

temperature too high or

too low.

Instrument faulty

Abide by the operating

temperature limits

Replace instrument

Err.11

Value could not be

calculated

Scaling incorrect

Check the setting and the

input signal