GB

WIKA operating instructions attachable indicator model A-AI-1

17

2018357.06 08/2012 GB/D

Offset and slope correction

The offset and slope correction is used to compensate for sensor tolerances

and for the fine adjustment of deviations of the transmitter or signal trans-

ducer.

To set the offset and slope correction, carry out the following:

While the actual value is being displayed, press key 3 for 2 seconds, until

"oFFS" appears in the display.

To set the parameter values, press keys 2 and 3.

To save the set value, press key 1. The parameter name will then appear in

the display once more.

To get to the next parameter to change, press key 1. The name of the

parameter will appear in the display.

Parameters Values

Description

Key 1

Keys 2 and 3

oFFS

Zero offset (offset)
-5.00 … 5.00 The input of the offset is made in digits. The set

offset value is subtracted from the measured value.

ScAL

Slope (scale)
-5.00 … 5.00 The input of the slope correction factor is made

in %. The displayed value is calculated as per the

following equation:

Display = (measured value - Offset - di.Lo) * (1 +

slope correction [% / 100] ) + di.Lo

Example for offset and slope correction

Connection of a pressure transmitter

The instrument display without offset and slope correction is as follows:

at 0 bar = 0.08, at 20 bar = 20.02

From this is calculated:

Zero point:

0.08

Slope:

20.02 – 0.08 = 19.94

Deviation:

0.06 = set slope - actual slope = 20.00 – 19.94

Therefore the following should be set:

Offset =

0.08 = zero error

Scale =

0.30 = deviation/actual slope = 0.06 /19.94 = 0.0030 = 0.30 %