WIKA operating instructions attachable indicator model A-AI-1

17

2018357.06 08/2012 GB/D

Offset and slope correction

The offset and slope correction is used to compensate for sensor tolerances

and for the fine adjustment of deviations of the transmitter or signal trans-

ducer.

To set the offset and slope correction, carry out the following:

■

While the actual value is being displayed, press key 3 for 2 seconds, until

"oFFS" appears in the display.

■

To set the parameter values, press keys 2 and 3.

■

To save the set value, press key 1. The parameter name will then appear in

the display once more.

■

To get to the next parameter to change, press key 1. The name of the

parameter will appear in the display.

Parameters Values

Description

Key 1

Keys 2 and 3

oFFS

Zero offset (offset)
-5.00 … 5.00 The input of the offset is made in digits. The set

offset value is subtracted from the measured value.

ScAL

Slope (scale)
-5.00 … 5.00 The input of the slope correction factor is made

in %. The displayed value is calculated as per the

following equation:

Display = (measured value - Offset - di.Lo) * (1 +

slope correction [% / 100] ) + di.Lo

Example for offset and slope correction

Connection of a pressure transmitter

The instrument display without offset and slope correction is as follows:

at 0 bar = 0.08, at 20 bar = 20.02

From this is calculated:

Zero point:

0.08

Slope:

20.02 – 0.08 = 19.94

Deviation:

0.06 = set slope - actual slope = 20.00 – 19.94

Therefore the following should be set:

Offset =

0.08 = zero error

Scale =

0.30 = deviation/actual slope = 0.06 /19.94 = 0.0030 = 0.30 %