Connection to shuttlebox x10, Fieldbus interface x15 – Lenze PCM 310 PCMatic Slot Controller Benutzerhandbuch
Seite 43

41
2.2.8. Connection to Shuttlebox X10
This interface is for connecting the PCMatic
®
-Shuttlebox. The 25-pole SUB-D connector is connected
in an identical way. As standard equipment, a 2 m connecting cable is included in the initial delivery.
Other lengths can be supplied on request. Alternatively, an adapter cable is available, to provide a
connection between the programming device and the Fieldbus. The pin allocation of the connector is
detailed below:
PIN Function PIN Function
1
+24 V
14
TXD PG
2
+24 V
15
RXD PG
3
+24 V
16
CTS PG
4
TXD Fieldbus diagnosis
17
RTS PG
5
RXD Fieldbus diagnosis
18
Alarm 2
6 GND 19
Alarm
1
7 GND 20
Start/Stop
switch
8 GND 21
Reset
PCM
9
LED ST1 (yellow)
22
Activate PCM UPS
10
LED RDY (yellow)
23
LED RUN PLC (green)
11
LED RUN (green)
24
CTS Fieldbus diagnosis
12
LED Status (yellow)
25
Power fail UPS
13
LED Error (red)
All LEDs are attached to a 5 V supply without a preliminary resistor. By use of the Fieldbus diagnosis, it
is also possible to transfer the Fieldbus configuration via PCMCon. The programming device interface
corresponds with the serial interface COM1. For the Start/Stop switch, 5 V corresponds with the Stop
status. For Reset PCM, 5 V corresponds with the Reset value. The UPS signals are used by the
PCMatic
®
-Shuttlebox.
2.2.9. Fieldbus interface X15
See Chapter on Technical Information