Register pcm-310, Read/write register pcm-310, Read-only register pcm-310 – Lenze PCM 310 PCMatic Slot Controller Benutzerhandbuch
Seite 55

53
4.9. Register PCM-310
4.9.1. Read/write register PCM-310
In this register, it is possible to write or read a byte at the location 208H.
Bit0 - WDOG Trigger
Bit1 - WDOG Enable
Bit2 - Reset Fieldbus module (1
⇒ Reset)
Bit3 - LED 2 (freely programmable; 0
⇒ on)
Bit4 - LED 1 (start/stop; 0
⇒ on)
Bit5 - RAM Bank 1
Bit6 - RAM Bank 2
Bit7 – UPS activation
4.9.2. Read-only register PCM-310
In this register, it is possible to read a word at the location 20AH.
Bit0 – 2 identification PCM-310 (1H)
Bit3 – Dip switch 1 (1
⇒ on)
Bit4 – 6 identification PCM-310 (3H)
Bit7 – Dip switch 2 (1
⇒ on)
Bit8 – WDOG is triggered
Bit9 – Host PC power (1
⇒ available)
Bit10 – ext. Power (via Shuttlebox; 1
⇒ available)
Bit11 – Battery status (1
⇒ OK)
Bit12 – Alarm input 1
Bit13 – Alarm input 2
Bit14 – 24 V power fail
Bit15 – Start / stop switch (0
⇒ start)