8.1. Profibus
DP
The PCMatic
®
card is equipped with a master module from the Hilscher company for operation with the
Profibus-DP.
The configuration of the Profibus requires the GSD files of the devices which are connected up and
their precise input and output parameters (e. g. 2 digital outputs and 4 analogue inputs). The GSD files
are as a rule available free of charge from the equipment manufacturer, or are delivered with the
equipment. These files must be located in the GSD register of PCMCon.
8.2.
Interbus - S
The PCMatic
®
card is equipped with a master module (Generation 4) from the Hilscher company for
use with Interbus-S.
The configuration of the Interbus can be undertaken automatically by reading in the connected devices.
This may also be done manually by feeding in the EDS files of the connected devices. To do this, the
EDS files must be located in the EDS register of PCMCon. In the following description, an automatic
configuration is assumed.
Example: Setting parameters for the Profibus with PCMCon
Select the menu
File/New
. Then select Profibus. In the menu
Insert/Master
, select COM-DPM.
After selecting the desired switching component group in the menu
Insert/Slave
, the parameters for
this can be set with
DP Slave Configuration
. The transfer procedure for the process data must be
set to
buffered, user-controlled
in the menu ‘Settings/DP Master settings. In the menu
Online/Download
, the
set configuration is saved to residual memory on the PCmatic. The
configuration is then complete.
Example: Setting parameters for the Interbus with PCMCon
Select the menu
File/New
. Then select Interbus auswählen. In the menu
Insert/Master
, select
COM-IBS.
After the connected switching component group has been automaticaly identified in the menu
Online/Automatic Network Scan
, this can be adopted with Automatic Configurati
on
. The transfer
procedure for the process data must be set to
buffered, user-controlled
in the menu
"Settings/Interbus master settings”. In the menu
Online/Download
the set configuration is saved to
residual memory on the Pcmatic. The configuration is then complete.