Fieldbus configuration – Lenze PCM 310 PCMatic Slot Controller Benutzerhandbuch
Seite 61

59
8. Fieldbus configuration
The configuration of the Fieldbus is undertaken by means of the system configuration tool
PCMCon
.
This program is delivered with the PCMatic
®
card and runs on the host computer. The configuration
can be carried out under WINDOWS95/98/2000 or NT. The preparation for the configuration is not
dependent upon the Fieldbus used and should be undertaken in the following steps.
1.
Hardware
setup
1.1 For ISA: enter PC basic address
X16
1.2 Switch to setting STOP
SW1
2.
Insert card in PC
2.1 Connect to 24 VDC supply
X1
2.2
Connect
to
Fieldbus
X15
3.
Configuration via bus
3.1 Start driver setup from PCMCon
3.2 Activate PCI support in CIF device driver setup
3.3 Boot up host PC
3.4
Start
PCMCon
Configuration via the serial interface
3.1 Attach serial connection cable to diagnostic interface
3.2 In PCMCon enter the serial interface via Setup/Device allocation
When undertaking the configuration via the bus, it should be ensured that the PCMatic
®
is switched on
first
and that the host PC is restarted
subsequently
.
In this way, the configuration can be completed independently of the Fieldbus and the special Fieldbus
type can be configured (Chapters 8.1 and 8.2). A comprehensive description can be found in the
manual for the PCMCon (on the CD).