Start-up submenu (standard), Start-up submenu (standard) 4.4.2 – Burkert Type 8681 Benutzerhandbuch
Seite 23

23
Software for Smartphone / PC
start-up submenu (standard)
4.4.2.
Type 8681 – Communicator
Rev. 2.4.0.0
Start-Up
Autotune 2
Autotune 1
Autotune 3
Autotune 4
Autotune 5
Autotune 6
Manual Control active?
Service indication active?
Parameter
Time
Cycles
Standard
Ranges
TEACHRESET DEV RESET
Use of external Ini S4
Opener
Closer
Screen: Start-up - Standard
By clicking on the �Autotune x” button, a description of the Autotune
•
function as well as the buttons
and
are indicated first
(details on the Autotune functions - see table below or in the operating
instructions)
don’t change the menu whilst the autotune process!
Set-up if
•
external initiator will be used as Opener (NC) or Closer (NO) -
according to the chosen external initiator
Indicates whether/which
•
service indication is active,
the service notification can be selected: after an elapsed time or after
elapsed cycles/switching operations or inactive (inactive = no ).
Click on the �Parameter� button to access the �Service� menu - see
description there - press the back arrow there to return to the �Start-up -
Standard� menu.
Indicates whether
•
manual control function is active, i.e. the
control head can be switched by magnetic manual actuation (valve 1).
“teacHreset”
•
button: after a warning message (
or
) all
teach positions are set to �not taught�.
“deV reset”
•
button: after a warning message (
or
) the
following values are reset to “0” (or �not taught”) with device reset:
- all Teach positions,
- the switching operations (cycles) counter V1-3,
- the operating-hours counter;
the standard values are reset:
- all tolerance values of the feedback areas of the position measuring
system
- the external initiator/proximity switch (as NO contact)
- manual actuation function (active)
- service notification time + switching operations (each inactive)
- parameter maintenance (V1=10000, V2=50000, V3=50000; 365 days)
Press
to return to SYSTEM mode.
autotune Function & Brief Description
autotune Function & Brief Description
autotune 1:
single-seated valves NC
Flap valves NC
Double-seated valves without clock function of valve
plate
autotune 4:
single-seated valves AA
Flap valves AA
autotune 2:
single-seated valves NO
Flap valves NO
autotune 5:
single-seated valves NC with three-position actuator
Flap valves NC with three-position actuator
autotune 3:
Double-seated valves with clock function of valve plate
autotune 6:
(Reserved function)
english
Type 8681