5 configuration and parameter tables – JUMO 707020 dTRANS T02 LCD - Four-Wire Transmitter Operating Manual Benutzerhandbuch

Seite 65

Advertising
background image

27

5 Configuration and parameter tables

Analog output

C114 Supply frequency/temperature compensation X

0

50Hz / internal temperature compensation

1

50Hz / fixed temperature compensation

2

60Hz / internal temperature compensation

3

60Hz / fixed temperature compensation

Para-

meter

Explanation

Value range factory

setting

X

C115 value with fixed

temperature
compensation

0 — 100°C

0

C116 Measurement display

X

0

percent

1

as output signal (mA or V)

2

in configurable unit
(see parameter C002 page 23)

C211 Function of the analog output

X

0

0 — 20mA

1

4 — 20mA

2

0 — 10V

3

2 — 10V

The limits can be inverted by swapping the two parameters

SCL and SCH.

C212 Signal of output on

probe break/short-circuit

X

0

positive (22mA or 11V - according to C211)

1

negative (0mA or 0V - according to C211)

Advertising