5 configuration and parameter tables – JUMO 707020 dTRANS T02 LCD - Four-Wire Transmitter Operating Manual Benutzerhandbuch
Seite 65
Advertising
27
5 Configuration and parameter tables
Analog output
C114 Supply frequency/temperature compensation X
0
50Hz / internal temperature compensation
1
50Hz / fixed temperature compensation
2
60Hz / internal temperature compensation
3
60Hz / fixed temperature compensation
Para-
meter
Explanation
Value range factory
setting
X
C115 value with fixed
temperature
compensation
0 — 100°C
0
C116 Measurement display
X
0
percent
1
as output signal (mA or V)
2
in configurable unit
(see parameter C002 page 23)
C211 Function of the analog output
X
0
0 — 20mA
1
4 — 20mA
2
0 — 10V
3
2 — 10V
The limits can be inverted by swapping the two parameters
SCL and SCH.
C212 Signal of output on
probe break/short-circuit
X
0
positive (22mA or 11V - according to C211)
1
negative (0mA or 0V - according to C211)