Installation / Preparation for commissioning

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Deutschland

Telefon +49 711 3409-0, Telefax +49 711 3409-133, E-Mail: [email protected]

37

English

5.9 Incremental interface

To output the absolute position, the standard version of the measuring system also
has an incremental interface in addition to the SSI interface.

•

The measuring system checks the outputs on this interface for external voltage

sources. The measuring system is shut down if voltages > 5.7 V arise. In this
state, the measuring system behaves as though it were not connected.

•

The interface is generally used for position feedback on motor control

applications.

NOTICE

Risk of damage to subsequent electronics due to
overvoltages caused by a missing earth reference
point!

•

If the earth reference point is missing entirely, e.g. 0 V

of the power supply is not connected, voltages equal
to the level of the supply voltage can occur at the
outputs of this interface.

•

An earth reference point must be guaranteed to be

present at all times.


5.9.1 Signal characteristic of the incremental interface

A corresponding number of pulses is output while completing a revolution. To
evaluate the count direction, a 2nd signal sequence with 90° phase offset is output for
the controller.

On the standard version, the incremental resolution of the measuring system is 4096
pulses / revolution. There is no zero pulse.