3 wiring a panel version, 4 wiring a wall-mounted version, Wiring a panel version – Burkert Type 8025 Benutzerhandbuch
Seite 23: Wiring a wall-mounted version

21
Installationandwiring
7.4.3
Wiring a panel version
Only move the selectors when the power supply is off.
→
Install the device as described in chap. “7.2”.
→
Set the selectors "SENSOR TYPE", "SENSOR SUPPLY" and "LOAD": see chap. “7.4.10”.
→
Before wiring the device insert the supplied cable clips into the slots of
the electronic board.
Figure 11:
Inserting the cable clips
→
Wire acc. to chap. “7.4.5” , “7.4.6”, “7.4.9” and “7.4.10”.
→
Secure the power supply cable, the flow sensor connection cable and, depending on the version, the relay
connection cables, with the cable clips.
7.4.4
Wiring a wall-mounted version
Only move the selectors when the power supply is off.
Insert the supplied stopper gaskets into the unused cable glands to ensure the tightness of the device.
• Unscrew the unused cable gland.
• Remove the transparent disk.
• Insert the supplied stopper gasket.
• Screw the nut of the cable gland.
→
Install the device as described in chap. “7.3”.
→
Set the selectors "SENSOR TYPE", "SENSOR SUPPLY" and "LOAD": see chap. “7.4.10”.
→
If the wall-mounted version is energized with a 115/230 V AC power supply, set selector E as shown in
“Figure 12”.
English
Type 8025 UNIVERSAL