36 v dc – Burkert Type 8025 Benutzerhandbuch
Seite 26

24
Installationandwiring
7.4.6
Wiring the Do1 transistor output of a panel version or a
wall-mounted version, 12-36 V Dc
Insert the supplied stopper gaskets into the unused cable glands to ensure the tightness of the device.
• Unscrew the unused cable gland.
• Remove the transparent disk.
• Insert the supplied stopper gasket.
• Screw the nut of the cable gland.
PE
PE
PE
L+
L-
PE P- P+
NC
Iout
PULSE
DO1
Supply
12..36Vdc
Univ
Batch
(AO1)
300 mA
+
-
12-36 V DC
(*)
+
-
+
- 5-36 VDC
PLC
Power supply of
the device
Power supply of
the device
PLC
PE
PE
PE
L+
L-
PE P- P+
NC
Iout
PULSE
DO1
Supply
12..36Vdc
Univ
Batch
(AO1)
300 mA
(*)
+
-
+
- 5-36 VDC
+
-
12-36 V DC
*) If a direct earth connection is not possible, fit a 100 nF/50 V capacitor between the negative power supply terminal and
the earth
Figure 18:
NPN wiring of the DO1 transistor output
Figure 19:
PNP wiring of the DO1 transistor output
7.4.7
Wiring the Ao1 current output of a wall-mounted version,
115/230 V Ac
Insert the supplied stopper gaskets into the unused cable glands to ensure the tightness of the device.
• Unscrew the unused cable gland.
• Remove the transparent disk.
• Insert the supplied stopper gasket.
• Screw the nut of the cable gland.
Only move the selectors when the power supply is off.
The 4-20 mA output can be wired in either sourcing or sinking mode.
English
Type 8025 UNIVERSAL