Operatingandcommissioning
8.6.10 configuring the transistor output Do1 to switch a load
depending on two threshold values
OUtPUt
DO1
hYStERES.
DO2
1-= 0.000
1+= 0.000
→
Enter a flow rate value
1)
, associated to the high
threshold, in the unit chosen in the "UNIT" parameter.
→
Confirm.
wiNDOw
→
Enter a flow rate value
1)
, associated to the low
threshold, in the unit chosen in the "UNIT" parameter.
→
Confirm.
iNV YES
iNV NO
0......9
→
Choose the operating, inverted or not inverted, of the
transistor output.
DEL. 1= 00
→
Enter the delay before switching (value between 0
and 99 s).
→
Confirm.
REtURN
On a version WITH relay outputs
On a version WITHOUT
relay outputs
FiLtER
1)
If hysteresis operating: value set for 1- ≤ value set for 1+.
If window operating: value set for 1- < value set for 1+.
Figure 38:
Configuration of the DO1 transistor output with switching thresholds
→
If you do not want to adjust another parameter, go to the "END" parameter of the Parameters menu and press
ENTER
to save the settings or not and go back to the Process level.