15 resetting both totalizers, Resetting both totalizers – Burkert Type 8025 Benutzerhandbuch
Seite 54

52
Operatingandcommissioning
The following table shows the response times (10% to 90%) for the filters:
Filter
Response time
Filter
Response time
0
0,15 s
5
6 s
1
0,7 s
6
10 s
2
1,4 s
7
19 s
3
2,5 s
8
33 s
4
3,5 s
9
50 s
Filter 0: measured
flow rate
Filter 3
Filter 6
Filter 9
slow
fast
Figure 45:
Available filters
→
If you do not want to adjust another parameter, go to the "END" parameter of the Parameters menu and press
ENTER
to save the settings or not and go back to the Process level.
8.6.15 Resetting both totalizers
This parameter makes it possible to reset both totalizers.
Both totalizers are reset upon confirmation of "SAVE YES" when leaving the Parameters menu.
tOtAL
RESEt N
CUtOFF
0......9
→
Choose to reset the two totalizers or not.
→
Confirm
RESEt Y
Figure 46:
Diagram of the "TOTAL" parameter of the Parameters menu
The daily totalizer can be reset from the Process level. See chap. 8.5.
→
If you do not want to adjust another parameter, go to the "END" parameter of the Parameters menu and press
ENTER
to save the settings or not and go back to the Process level.