1 adjusting the current output, Adjusting the current output – Burkert Type 8025 Benutzerhandbuch
Seite 57

55
Operatingandcommissioning
8.7.1
Adjusting the current output
This parameter makes it possible to adjust the value of the current transmitted on the analogue output.
CAL AO1
OFFSEt
FREQUENC.
OF= 4.00
→
The device generates a 4 mA current.
→
Measure the current given on the 4-20 mA output using a multimeter.
→
Enter the value displayed by the multimeter. The permitted offset range is 3 to
5 mA.
→
Confirm.
SPAN
SP= 20.00
→
The device generates a 20 mA current.
→
Measure the current given on the 4-20 mA output using a multimeter.
→
Enter the value displayed by the multimeter. The permitted span range is 18,50 to
21,50 mA.
→
Confirm.
VALiD N/Y
→
Confirm the entered values or not.
Figure 50:
Diagram of the "CAL AO1" of the Test menu
→
If you do not want to adjust another parameter, go to the "END" parameter of the Test menu and press
ENTER
to save the settings or not and go back to the Process level.
English
Type 8025 UNIVERSAL