50

Operatingandcommissioning

8.6.12 configuring the relay outputs Do2 and Do3 to switch a

load depending on two thresholds

The hysteresis or window operation is detailed in “Figure 39”, chap. “8.6.8”.

OUtPUt

DO2

hYStERES.

DO3

2-= 0.000

2+= 0.000

→

Enter a flow rate value

1)

, associated to the high

threshold, in the unit chosen in the "UNIT" parameter.

→

Confirm.

wiNDOw

→

Enter a flow rate value

1)

, associated to the low

threshold, in the unit chosen in the "UNIT" parameter.

→

Confirm.

iNV YES

iNV NO

0......9

→

Choose the operating, inverted or not inverted, of the
relay output.

DEL. 2= 00

→

Enter the delay before switching (value between 0
and 99 s).

→

Confirm.

Configure the DO3 relay out-

put the same way as the DO2

relay output.

1)

If hysteresis operating: Value set for 2- respectively 3- ≤ Value set for 2+ respectively 3+.

If window operating: Value set for 2- respectively 3- < Value set for 2+ respectively 3+.

Figure 42:

Configuration of the DO2 or DO3 relay output with switching thresholds