WIKA FLM Benutzerhandbuch

Seite 17

Advertising
background image

GB

WIKA operating instructions level sensor model FFG

17

13445627.01 12/2010 GB/D/F

5. Electrical connection

The level sensor system now is in the adjusting mode with the green

LED (4) "Cal/Err" flashing. The current consumption of the level sensor

is 12 mA. Without pressing the key again, the level sensor remains in the

adjusting mode for 20 seconds before changing back to the measuring

mode without modifying the adjustment.

To fix the 4 mA point within this period

move the float to the desired position,

and press down key "4 mA" (2) for a short period of time

(0.1 ... 2 seconds)

The LED display will disappear for 5 seconds, with the current consump-

tion being 4 mA, and thereafter again 12 mA. The level sensor will

remain in the adjusting mode for another 15 seconds before changing

back to the gauging mode.

Fig. 6: Adjustment

To fix the 20 mA point within this period

advance the float to the desired position,

and press down key "20 mA" (3) for a short period of time

(0.1 ... 2 seconds)