WIKA operating instructions level sensor model FFG

13445627.01 12/2010 GB/D/F

The LED display will disappear for 5 seconds, with the current consump-

tion of the level sensor being 20 mA, and thereafter again 12 mA. The

level sensor will remain in the adjusting mode for another 15 seconds

before changing back to the gauging mode.

The new adjustment will not be adopted until it automati-

cally changes from the adjusting mode into the measuring

mode (with LED disappearing). For this reason, the level

sensor should not be cut off from the current supply before.

Current Consumption in the error mode

If the level sensor is due to a failure unable to determine a proper float

position, i.e. a correct filling level, it will change to an error mode after a

short period of time. The current consumption in the error mode has been

adjusted, ex factory, to 21.5 mA although it can be switched to 3.6 mA,

also.
For adjusting the current consumption in the error mode

(see Fig. 5), proceed as follows

unscrew lid (1) of probe head with open-end wrench hold both "4 mA"

(2) and "20 mA" keys (3) simultaneously in pressed for a period of

time of no less than 3 seconds. The green LED (4) "Cal/Err" is flashing

fast, with the current consumption being 16 mA. LED, after 5 seconds,

will cease to flash, displaying, for 2.5 seconds, the set error current

consumption. Once the LED is permanently illuminated, I error =

21.5 mA; once it extinguishes I error = 3.6 mA. With the key not being

pressed down again, the level sensor will remain in the error mode

for another 2.5 seconds before changing back into the gauging mode

without modifying the adjustment. For setting a current consumption of

3.6 mA during the 10-second dwelling time in the error mode

briefly press down the key "4 mA" key (2) (for 0.1 ... 2 seconds). For

adjusting a current consumption of 21.5 mA during the 10-second

dwelling time in the error mode

briefly press down the "20 mA" key (3) (for 0.1 ... 2 seconds).

The new adjustment will not be adopted by the level sensor

until it automatically changes from the adjusting mode to the

gauging mode (with LED disappearing). The level sensor

should, therefore, not be cut off from the power supply before.

5. Electrical connection