WIKA operating instructions level sensor model FFG

5

13445627.01 12/2010 GB/D/F

Prior to starting operation please check all devices for their proper

connection, operability and power supply; this shall also apply to

assemblies coupled thereto.

The general operating instructions of all devices as used must be

abided by.

Measures should be taken preventing personal injuries and damage

to property from occurring in case of a defective condition of the level

sensor system.

The level sensor system must not be operated in the direct vicinity of

strong electromagnetic fields (minimum distance: 1 m).

The level sensor system must not be exposed to heavy mechanical

strain.

The maximum power and voltage values for the intrinsically safe

operation as specified in the assembling and operating instructions

should be adhered to.

The safe operation of the system with a view to

pressure and temperature of the materials as emplo-

yed shall be Operator’s responsibility.

As even in case of failure, the guide tube does not exhibit a

source of ignition there are no objections, in terms of safety,

to use the sensor (float and guide tube) as an operating

unit of the 1/2 category with containers for combustible

fluids (except for carbon disulphide and silicon-organic

compounds) under varying atmospheric conditions at

excess pressures of up to 25 bar and temperatures of

between -60 ... +250 °C.