English, Technical data – Burkert Type 3002 Benutzerhandbuch
Seite 7

3001S / 3002S - 5
english
Technical data
Mechanical data
Housing material
polycarbonate
Rated load torque
Type 3001 S
Type 3002 S
50 Nm
135 Nm
Folding square
90°
Floating time [s/90°]
28 s
Shaft end
square socket
Ambient temperature
standard with auxiliary
function
-20 to +50 °C
-10 to + 50 °C
Versions
standard on
inquiry
2-position actuator
3-position actuator
Mass
Type 3001 S
Type 3002 S
ca. 3.6 kg
ca. 4.0 kg
Auxiliary functions
- torque limit
- automatic resetting with power failure
Electrical Data
Operating voltage
12, 24 V DC
120 V/50-60 Hz
230 V/50-60 Hz
Voltage tolerance
± 10 %
Capacity
AC
DC
with auxiliary functions
55 W
20 W
40 W
Type of rating
AC
UC/DC
with auxiliary functions
Intermittent operation 50% ED
Continuous operation 100% ED
Continuous operation 100% ED
Electrical connection
Device plug sockets for cable
6-7 mm or cable gland
Pg 11 according to DIN 46 32
Protection class
IP 65
Limit switch
single-pole change over switch, max. 250 V/10 A
Potentiometer
R= 1k
, max. 2 W
Standard signal input
4 to 20 mA
0 to 10 V
R
input
< 50
R
input
> 10 k
Accuracy during
standard signal control
Linearity deviation
Hysteresis
< ± 1,5 %
< ± 1,5 %