3 Product application for
- emergency off-relays
-
safety gate monitoring relay
-
with time delayed
a) SAFE TA / TN / TR / TU
Dual-channel emergency stop
If the start bottom will be pressed and released
the output contacts 13-14, 23-24, 47-48 and 57-
58 will be closed. After the pressing the
emergency stop switch the contacts 13-14 and
23-24 will open immediately. The contacts 47-48
and 57-58 remains close during the selected
time delay. Before the time delayed contact are
not open a restart is not possible.(except SAFE
TR)
Suitable up to category 4; SIL3; PLe reachable
(immediate switching) Suitable up to risk
category 4 (time delayed output)
Single-channel emergency stop
If the start bottom will be pressed and released
the output contacts 13-14, 23-24, 47-48 and 57-
58 will be closed. After the pressing the
emergency stop switch the contacts 13-14 and
23-24 will open immediately. The contacts 47-48
and 57-58 remains close during the selected
time delay. Before the time delayed contact are
not open a restart is not possible. (except SAFE
TR)
Suitable up to category 4; SIL3; PLe reachable
(immediate switching) ** Suitable ut to risk
category 4 (time delayed output) **
Dual channel protection door monitoring
If the safety switches S1 and S2 are closed and
the start bottom will be pressed and released
then the output contacts 13-14, 23-24, 47-48
and 57-58 will be closed. With automatic start
S34-S35 they will be closed after closing the
safety switches. After the opening of the safety
switches the contacts 13-14 and 23-24 will open
immediately. The contacts 47-48 and 57-58
remains close during the selected time delay.
Before the time delayed contact are not open a
restart is not possible. (except SAFE TR)
Suitable up to category 4; SIL3; PLe reachable
(immediate switching) Suitable up to risk
category 4 (time delayed output)