Troubleshooting

Note

The required vacuum may not be generated if there is an insufficient supply of air to the

valve terminal.

Malfunction

Possible cause

Remedy

Workpiece does not

release from the

suction cup

A vacuum has built up when lifting

large suction cups quickly

Increase the duration and

intensity of the ejector pulse

Lift the suction cup slower from

the workpiece

Actively set the ejector pulse

when lifting the suction cup

The tubing used between the suction

cup and vacuum module is sized

incorrectly (tubing is too long and/or

internal diameter is too small)

Replace the tubing

Tubing requirements

section 4.2

Flow control screw is closed

Open the flow control screw

No display

Supply voltage not applied or no

permitted operating voltage

Switch on supply voltage / maintain

permitted operating voltage range

Electrical connections swapped

(incorrect polarity)

Wire in accordance with the circuit

diagram

Device defective

Replace the device

Incomplete display

Display defective

Replace the device

Outputs do not

switch according to

settings

Short circuit/overload at relevant

output

Eliminate short circuit/overload

Device defective

Replace the device

Settings cannot be

edited (“Lock” in the

display)

Access protection active

Enter the security code (if the

security code has been lost, reset the

device to the factory settings

section 7.3 )