2450786.06 GB/D 10/2010

56 WIKA Operating instructions/Betriebsanleitung D-10-9, D-11-9

2450786.06 GB/D 10/2010

57

WIKA Operating instructions/Betriebsanleitung D-10-9, D-11-9

Index Sub-

index Object Name

Type

Attr Default-

Value

Remarks

9121 h

array

AI_Input_Scaling_1_PV

0

var

number of entries

unsigned 8

ro

01 h

1

var

AI_Input_Scaling_1_PV_1 integer 32

rw

AI_Span_Start *

9123 h

array

AI_Input_Scaling_2_PV

0

var

number of entries

unsigned 8

ro

01 h

1

var

AI_Input_Scaling_2_PV_1 integer 32

rw

AI_Span_End *

9124 h

array

AI_Input_Offset

0

var

number of entries

unsigned 8

ro

01 h

1

var

AI_Input_Offset_1

integer 32

rw

00 h

*

9130 h

array

AI_Input_PV

0

var

number of entries

unsigned 8

ro

02 h

1

var

AI_Input_PV_1

integer 32

ro

pressure value

2

var

AI_Input_PV_2

integer 32

ro

temperature value

9148 h

array

AI_Span_Start

0

var

number of entries

unsigned 8

ro

02 h

1

var

AI_Span_Start_1

integer 32

ro

min. operating

pressure (Pa)

2

var

AI_Span_Start_2

integer 32

ro

min. operating

temperature (°C)

9149 h

array

AI_Span_End

0

var

number of entries

unsigned 8

ro

02 h

1

var

AI_Span_End_1

integer 32

ro

max. operating

pressure (Pa)

2

var

AI_Span_End_2

integer 32

ro

max. operating

temperature (°C)

* write only if calibration access

7. Starting, operation / Inbetriebnahme, Betrieb

D

GB

Object 2006: Pressure Overflow Count
This object records the number of times the pressure process value
(object: 9130 01) exceeds the span end value (object 9149 01).
The hysteresis is 5 % of the operating pressure range. This value is non-volatile and is in-
tended to log the number of times the transducer is subjected to pressures outside the opera-
ting range. The entry is read/write and hence can be reset at any time (e.g. after calibration).

Object 2007: Pressure Underflow count
This object records the number of times the pressure process value
(object: 9130 01) is less than the span start value (object 9148 01). The hysteresis is 5 % of the
operating pressure range. This value is non-volatile and is intended to log the number of times
the transducer is subjected to pressures outside the operating range. The entry is read/write a
hence can be reset at any time (e.g. after calibration).

Object 2008: Temperature overflow count
This object records the number of times the temperature process value
(object: 9130 02) exceeds the span end value (object 9149 02). The hysteresis is 5 °C. This
value is non-volatile and is intended to log the number of times the transducer is subjected to
temperatures outside the operating range. The entry is read/write and hence can be reset at
any time (e.g. calibration).

Object 2009: Temperature underflow count
This object records the number of times the temperature process value
(object: 9130 02) is less than the span start value (object 9148 02). The hysteresis is 5 °C. This
value is non-volatile and is intended to log the number of times the transducer is subjected to
temperatures outside the operating range. The entry is read/write and hence can be reset at
any time (e.g. calibration).

D: Nachfolgende Beschreibung ist in englischer Sprache, gemäß der CiA-Definition !

Object Directory-Description of Manufacturer Specific Profile

7. Starting, operation / Inbetriebnahme, Betrieb

D

GB