2450786.06 GB/D 10/2010

14 WIKA Operating instructions/Betriebsanleitung D-10-9, D-11-9

2450786.06 GB/D 10/2010

15

WIKA Operating instructions/Betriebsanleitung D-10-9, D-11-9

ID

DLC

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

580h +

Nodeld

8

CMD =

60h

23h

91h

01h

00h

00h

00h

00h

ID

DLC

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

600h +

Nodeld

8

CMD =

22h

23h

91h

01h

90h

D0h

03h

00h

Index 9123h

Subindex 1

desired value (as integer32)

ID

DLC

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

580h +

Nodeld

8

CMD =

60h

21h

91h

01h

00h

00h

00h

00h

ID

DLC

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Byte 8

600h +

Nodeld

8

CMD =

22h

21h

91h

01h

70h

A0h

FEh

FFh

Index 9121h

Subindex 1

desired value (as integer32)

Example 1:

Pressure range: -1 ... 2.5 bar (=> -100,000 ... 250,000 Pa output value)

Calibration Point 1:

Pressure applied (reference value): -0.9 bar

The user writes the value that the device is supposed to indicate under the pressure currently
applied to object 9121h subindex 1 (AI_Input_Scaling_1_PV), i.e. in this example -90,000 Pa
(=> FF FE A0 70 h)

The changed parameters are not automatically stored, but they have to be stored via object
1010h Store Parameters. Furthermore the device can be reset to the factory settings via object
1011h Restore Default Parameters.

7. Starting, operation

GB

7. Starting, operation

GB

The pressure transmitter confirms the successful service by:

Calibration Point 2:

Pressure applied (reference value): 2.5 bar

The user writes the value that the device is supposed to indicate under the pressure currently
applied to object 9123h subindex 1 (AI_Input_Scaling_2_PV), i.e. in this example 250,000 Pa
(=> 00 03 D0 90 h)

The pressure transmitter confirms the successful service by: