Specifications

Model D-10-9 / D-11-9

Temperature coefficients within

compensated temp range

(The temperature related deviations in the range 0 ... +50 °C /

+32 ... +122 °F are already included in the accuracy)

„

Mean TC of zero

% of span

0.20 / 10 K {0.10}

„

Mean TC of range

% of span

0.20 / 10 K {0.10}

CE- conformitiy

„

Pressure equipment directive

97/23/EC

„

EMC directive

2004/108/EC, EN 61 326 Emission (Group 1, Class B) and Immunity

(industrial locations)

Shock resistance

g

< 100 according to IEC 60068-2-27 (mechanical shock)

Vibration resistance

g

< 5 according to IEC 60068-2-6 (vibration under resonance)

Wiring protection

„

Reverse polarity protection

UB+ towards UB-

Weight

kg

Approx. 0.4

1

2

3

4

5

6

7

8

9

10

ON

OFF

Functional test

„

Open pressure connections only after the system is without pressure!

„

Observe the ambient and working conditions outlined in section 7 „Technical
data".

„

Please make sure that the pressure transmitter is only used within the over-
load threshold limit at all times!
When touching the pressure transmitter, keep in mind that the surfaces of
the instrument components might get hot during operation.

When designing your plant, take into account that the stated values (e.g.burst pressure,
over pressure safety) apply depending on the material, thread and sealing element used.

The output signal must be proportional to the pressure. If not, this might point to a
damage of the diaphragm. In that case refer to chapter 10 „Troubleshooting“.

7. Starting, operation

GB

*)

In an oxygen version model D-11-9 is not available. In an oxygen version model D-10-9 is only available with media temperatures

between -4 … +140 °F / -20 … +60 °C.
{ } Items in curved brackets are optional extras for additional price.

DIP switch Assignment

7. Starting, operation

GB

LSB

DIP switch 1 to 5:

Address settings, address 1...31

DIP switch 6:

Baud rate

ON=User defined bitrate

OFF=250kBd

DIP switch 7:

Settings

ON:

acc.to DIP switch

OFF:

from memory inside the instrument

DIP switch 8:

Switching of measuring value output

ON:

currently configurated PDO is sent

every 10 ms (e.g. for diagnostic purposes)

OFF:

Output depending on settings in object directory

DIP switch 9 and 10:

Termination

ON: terminating resistor switched on

OFF:

terminating resistor switched off

Factory default settings: DIP switch 1-10: OFF