Error display, Initial start-up and operation gb, Operating instructions/betriebsanleitung, wud-2x – WIKA WUD-26 Benutzerhandbuch
Seite 16

Operating instructions/Betriebsanleitung, WUD-2x
11611057.01 GB/D 11/2013
16
1. LED (red) - Status Switch Output 1
2. LED (red) - Status Switch Output 2
3. LED (red) - Ready LED
Parameter
Parameter
Description
SP1 / SP2
Hysteresis function: Switch point, switch output (1 or 2)
RP1 / RP2
Hysteresis function: Reset point, switch output (1 or 2)
EF
Enhanced Programming Functions
RES
Return the set parameter to the Factory Settings
DS1
Switch Delay Time, which must occur without interruption before any electrical signal change occurs (SP1 or SP2)
DS2
DR1
Switch Delay Time, which must occur without interruption before any electrical signal change occurs (RP1 or RP2)
DR2
OU1
Switching Function Switching Output (1 or 2)
OU2
OFF = always off
ON = always on
NO = normally open
NC = normally closed
DISU
Display-Update 0.2, 0.5, 1, 5, 10, 60 seconds
DISO
Display zero point offset (± 10 % of full scale)
(This setting has no effect on the ouput signal. Only the displayed value will be set.)
Error Display
Error
Description
ATT
Setting out of range (Acknowledgement of an error display by pressing the main key)
OL
Overpressure, measuring range exceeded > approx. 5% (Display flashing)
UL
Underpressure, under measuring range < approx. 2% (Display flashing)
7. Initial start-up and operation