Operating instructions/Betriebsanleitung, WUD-2x

11611057.01 GB/D 11/2013

16

1. LED (red) - Status Switch Output 1

2. LED (red) - Status Switch Output 2

3. LED (red) - Ready LED

Parameter

Parameter

Description

SP1 / SP2

Hysteresis function: Switch point, switch output (1 or 2)

RP1 / RP2

Hysteresis function: Reset point, switch output (1 or 2)

EF

Enhanced Programming Functions

RES

Return the set parameter to the Factory Settings

DS1

Switch Delay Time, which must occur without interruption before any electrical signal change occurs (SP1 or SP2)

DS2
DR1

Switch Delay Time, which must occur without interruption before any electrical signal change occurs (RP1 or RP2)

DR2
OU1

Switching Function Switching Output (1 or 2)

OU2

OFF = always off

ON = always on

NO = normally open

NC = normally closed

DISU

Display-Update 0.2, 0.5, 1, 5, 10, 60 seconds

DISO

Display zero point offset (± 10 % of full scale)

(This setting has no effect on the ouput signal. Only the displayed value will be set.)

Error Display

Error

Description

ATT

Setting out of range (Acknowledgement of an error display by pressing the main key)

OL

Overpressure, measuring range exceeded > approx. 5% (Display flashing)

UL

Underpressure, under measuring range < approx. 2% (Display flashing)