6. Commissioning, operation / 7. Information on mounting ...

11419904.02 09/2013 GB/D

WIKA operating instructions models TR12, TC12 (Ex d)

19

6.2 Electrical connection

Variant 1

For the electrical specifications (e.g. connection diagrams, tolerance values, etc.) please

refer to the data sheets TE 60.17 (for TR12) and TE 65.17 (for TC12).

Variant 2

For the electrical specifications (e.g. connection diagrams, tolerance values, etc.) please

refer to the relevant operating instructions and/or data sheet for the built-in head-mounted

transmitter.

Variant 3

For the electrical specifications (e.g. connection diagrams, tolerance values, etc.) please

refer to the relevant operating instructions and/or data sheet for the built-in Ex d field

transmitter.

Variant 1 and 2

Junction between Ex d cable gland and connection head

Threads M20 x 1.5: tightening torques 12 Nm

Threads ½ NPT: tightening torques 30 Nm

Junction between cable and Ex d cable gland

Screw the male nut tightly into the adapter (use appropriate tools!)

During installation, take care to

Avoid distorting the cable sheath when tightening the male nut.

Avoid cutting too deep into the cable sheath.

Use suitable cable.

Be careful of the clamping zone of the cable gland.

7. Information on mounting and operation in hazardous areas

WARNING!

Non-observance of these instructions and their contents may result in the loss

of explosion protection.

The requirements of the 94/9/EC (ATEX) directive must be followed. Additionally

the specifications of the respective national regulations concerning Ex usage

(e.g. EN/IEC 60079-10 and EN/IEC 60079-14) apply.