Maintenance and cleaning / 11. faults, Faults – WIKA TR12-M Benutzerhandbuch

Seite 27

Advertising
background image

GB

10. Maintenance and cleaning / 11. Faults

11419904.02 09/2013 GB/D

WIKA operating instructions models TR12, TC12 (Ex d)

27

10.3 Calibration, recalibration

It is recommended that the measuring insert is recalibrated at regular intervals (resistance

thermometers: approx. 24 months, thermocouples: approx. 12 months). This period can

reduce, depending on the particular application. The calibration can be carried out by the

manufacturer, as well as on site by qualified technical staff with calibration instruments.

11. Faults

Faults

Causes

Measures

No signal/line break

Mechanical load too high or

overtemperature

Replacement of the sensor or the

measuring insert with a suitable version

Erroneous measured

values

Sensor drift caused by overtemperature Replacement of the sensor or the

measuring insert with a suitable version

Sensor drift caused by chemical attack Use of a suitable thermowell

Erroneous measured

values (too low)

Entry of moisture into cable or measuring

insert

Replacement of the sensor or the

measuring insert with a suitable version

Erroneous measured

values and response

times too long

Wrong mounting geometry, for example

mounting depth too deep or heat

dissipation too high

The temperature-sensitive area of the

sensor must be inside the medium,

and surfaces measurements must be

ungrounded

Deposits on the sensor or thermowell

Remove deposits

Erroneous measured

values (of thermocouples)

Parasitic voltages (thermal voltages,

galvanic voltage) or wrong equalisation

line

Use of a suitable equalisation line

Display of measured

value jumps

Cable break in connecting cable or

loose contact caused by mechanical

overload

Replacement of the sensor or

measuring insert with a suitable design,

for example fitted with strain relief or a

thicker conductor cross-section

Corrosion

Composition of the medium not

as expected or modified or wrong

thermowell material selected

Analyse medium and then select a

more-suitable material or replace

thermowell regularly

Signal interference

Stray currents caused by electric fields

or earth loops

Use of screened connecting cables,

increase in the distance to motors and

power lines

Earth circuits

Elimination of potentials, use of

galvanically isolated transmitter supply

isolators or transmitters

CAUTION!

If faults cannot be eliminated by means of the measures listed above, the

instrument must be shut down immediately, and it must be ensured that signal

is no longer present, and it must be prevented from being inadvertently put back

into service. In this case, contact the manufacturer.

If a return is needed, follow the instructions given in chapter 12.2 “Return”.