Hand-Held Pendant Station

HBAS-094594

095640-02-02/06

Subject to technical modifications

Page 19 / 40

6. Signaling

6.1 Acoustic signaling (command byte 52H)

An acoustic transducer is integrated into the hand-held pendant station. This can be
operated from the control system. For this purpose the command byte

52H

must be sent

with the related parameters.

Command byte Description

Parameter:

52H

Continuous sound on
Continuous sound off
Pulsed sound on (frequency 1Hz)
Pulsed sound 0.1s

30H
31H
32H
33H

Example: Switch on pulsed sound

HBAS

DLE

DLE

Control
system

STX

52H

32H

DLE

ETX

BCC

If an incorrect parameter is entered, the error byte is set to 34H.
The error byte can be polled using the status polling (section 9.1).

6.2 Optical signaling: Status LED

The Status LED signals internal program information. The user cannot access the way
the LED is operated.

The following information is signaled:

Status LED

Function

Continuously
illuminated

Data transfer active

Flashing 0.5Hz Data transfer inactive, HBAS ready for initialization

Flashing 2 Hz

Hand-held pendant station in configuration mode

Flashing 4 Hz

Communication error

1)

1)

If the attempt to establish the connection from the HBAS to the control system is

unsuccessful, or if an existing connection is broken off (see section 3), then
the hand-held pendant station enters the error state and the Status LED flashes at
a frequency of 4 Hz.