WIKA operating instructions resistance thermometers and thermocouples, Ex n

GB

J) Electrical screening may only be grounded at one end, and outside of the Ex area.

The housing must be grounded against electromagnetic fields and electrostatic discharge.

Mounting within metallic enclosures:

The screen must be fully coupled to the equipotential bonding of the connected enclosure.

Mounting within non-metallic enclosures:

All electrically connected thermometer components within the hazardous area must be

provided with equipotential bonding.

K) When mounting thermometers with flying leads (e.g. models TR40, TC40, TR50, TC50),

installation personnel must ensure that installation is carried out properly and in compliance

with the appropriate regulations.

7.1.1 Special conditions of use (X conditions)
A) Equipment category classification

Max. surface

temperature and

temperature class

Max. temperature in °C

at the thermowell /

measuring insert

Minimum neck

length Mh

1)

Ambient

temperature

range T

a

2)

T80 °C or T6

78

-

-20 ... +55 °C

T95 °C or T5

93

-

-20 ... +70 °C

T130 °C or T4

128

20 mm

-20 ... +80 °C

T195 °C or T3

193

50 mm

-20 ... +80 °C

T290 °C or T2

288

100 mm

-20 ... +80 °C

T440 °C or T1

438

100 mm

-20 ... +80 °C

1) The minimum neck length is defined as the distance between the lower edge of the connection head and the

heat-emitting surface.

2) The ambient temperature range, Tamb, may be further limited by the transmitter fitted.

B) The models TR40, TC40, TR50, TC50 cable probes must be fitted with kink protection, strain

relief and mechanical protection.

C) The models TR40, TC40, TR50, TC50 cable probes should only be operated up to the

transition sleeve in hazardous areas. The connection side (plastic piping) must be kept outside

of the hazardous area.

D) The models TR40, TC40, TR50, TC50 cable probes must be connected to ground through

their installation.

E) The transmitter used must have a valid declaration in accordance with the 94/9/EC guidelines,

related to their equipment classification (see table “Equipment category classification”).

F) The temperature resistance of the connecting cables, the connection heads, the cable entries

and if necessary the blanking connectors must be at least as high as the max. permissible

ambient temperature.

7. Information on mounting and operation in hazardous areas