WIKA operating instructions resistance thermometers and thermocouples, Ex n

GB

8. Electrical connection values

8.1 Electrical data without built-in transmitter or digital display

Power and signal circuit

U

max

= 30 V

I

max

= 9 mA

P

max

= 15 mW

Marking

II 3G Ex nA IIC T1…T6 Gc X

II 3D Ex tc IIIC T440°C …T80°C Dc X

8.2 Electrical data for built-in transmitters or digital displays

Power and signal circuit

U

max

= 40 V

The transmitter used must be certified

and confirmed to EN 60079-15.

I

max

= 150 mA

P

max

= 1,000 mW

Sensor current loop

I

max

= 9 mA

P

max

= 15 mW

Marking

II 3G Ex nA IIC T1…T6 Gc X

II 3D Ex tc IIIC T440°C …T80°C Dc X

The transmitters and digital displays used must have their own certification in accordance

with EN/IEC. The installation conditions and electrical connection values can be seen from the

relevant approvals and must be observed.

9. Maintenance and cleaning

9.1 Maintenance

This thermometer is maintenance-free.

Repairs must only be carried out by the manufacturer.

9.2 Cleaning

CAUTION!

Clean the instrument with a moist cloth.

Electrical connections must not come into contact with moisture.

Wash or clean the dismounted instrument before returning it, in order to protect

personnel and the environment from exposure to residual media.

Residual media in dismounted instruments can result in a risk to persons, the

environment and equipment. Take sufficient precautionary measures.

For information on returning the instrument see chapter 11.2 “Return”.