Electrical connection – WIKA TIF52 Benutzerhandbuch

Seite 20

Advertising
background image

20

WIKA operating instructions models TIF50, TIF52

GB

14009686.02 03/2012 GB/D

Configure the input of the transmitter appropriately for the thermocouple type and the cold

junction compensation actually used, otherwise measurement errors may be caused (see

chapter 6.2 "Configuration").

Should the cold junction compensation be operated with an external resistance

thermometer (2-wire connection), connect this to terminals  and .

7.1.3 Voltage source

Make sure that the mV sensor is connected with the correct polarity.

7.1.4 Potentiometer

Connection of a potentiometer is possible.

7.2 Power supply, 4 ... 20 mA current loop

The model TIFxx field instrument is a 2-wire temperature transmitter; depending on the

version, it can be supplied with various types of power supply. Connect the positive pole of

the power supply to the terminal marked with ⊕ and the negative pole of the power supply

to the terminal marked with ⊖.

With flexible leads we recommend the use of crimped connector sleeves.

The integrated reverse polarity protection (wrong polarity on the terminals ⊕ and ⊖)

prevents the transmitter from damage. The following maximum values are applicable:

Model TIFxx-S: DC 42 V

Model TIFxx-I: DC 29 V

Model TIFxx-F: DC 30 V

The model TIFxx field instrument requires a minimum terminal voltage of DC 13.5 V. The

load must not be too high as, otherwise, in the case of relatively high currents, the terminal

voltage at the transmitter will be too low.

The model TIFxx field instrument is equipped with terminal voltage monitoring ('under-

voltage' detection). If too small a voltage is detected at the terminal (< 13.5 V) the error is

signalled on the output (< 3.6 mA).

7. Electrical connection

Advertising