WIKA operating instructions models TIF50, TIF52
GB
14009686.02 03/2012 GB/D
8.1 Main menu "Measurement"
Function
Factory setting
Unit
Setting the unit of the measuring range of the connected transmitter
Setting range:
mA → Ω → bar → mbar → PSI → hPa → kPa → mmH
2
O → mH
2
O → inHG → °C → °F
→ K → % → USER → V
mA
Measuring range start
Setting of the start value of the measuring range of the connected transmitter
(e.g. -30 for a measuring range of -30 ... +120 °C)
Setting range: -9999 ... 99999
4,000
Measuring range end
Setting the end value of the measuring range of the connected transmitter
(e.g. 120 for a measuring range of -30 ... +120 °C)
Setting range: -9999 ... 99999
20,000
Measuring range format
Setting the decimal point for the measuring range of the connected transmitter.
Setting range: 0 ↔ 0.0 ↔ 0.00 ↔ 0.000 ↔ 0.0000
00.000
Span (only DIH5x-B, DIH5x-Z, DIH62-B, DIH62-Z)
The current measured value is applied as max. adjustment for the sensor.
Attention: Cannot be used for all HART
®
transmitters
-----
Zero point (only DIH5x-B, DIH5x-Z, DIH62-B, DIH62-Z)
The current measured value is applied as min. adjustment for the sensor.
Attention: Cannot be used for all HART
®
transmitters
-----
Damping (only DIH5x-B, DIH5x-Z, DIH62-B, DIH62-Z)
Input damping for damping the measured value.
Setting range: 0.0 … 999
0.0
Adress (only DIH5x-B, DIH5x-Z, DIH62-B, DIH62-Z)
Setting the HART
®
address of the assigned transmitter in the multidrop mode;
for the standard current loop mode, this address must always be set to 0.
Setting range: 0 ... 15
0