9. Information on mounting and operation in hazardous areas

In hazardous areas, only use field instruments that are approved for those hazardous

areas. The approval is marked on the product label.

When connecting them to other devices or component, observe the connection

requirements regarding explosion protection, such as maximum admissible voltage, power

or load with capacitances (see chapter 9.1 "Model overview and their approvals" and

9.2 "Special conditions for safe use models TIF50-F, TIF52-F").

9.1 Model overview and their approvals

Model

Explosion protection and approval number

Ignition protection type

TIF50-F

TIF52-F

BVS 10 ATEX E 158

II 2G

II 2G

IECEx BVS 10.0103

Ex d IIC T6/T5/T4 Gb

Ex db IIC T6/T5/T4

Ex d IIC T6/T5/T4 Gb

Ex db IIC T6/T5/T4

Flameproof enclosure

TIF50-I

TIF52-I

BVS 10 ATEX E 016 X

II (1) 2G

II (1) 2D

II 2D

II 2D

IECEx BVS 10.0037X

Ex ia [ia Ga] IIC T4/T5/T6 Gb

Ex ia [ia Da] IIIC T120°C Db

Ex ia IIC T4/T5/T6 Gb

Ex ia IIIC T120 °C Db

Intrinsically safe equipment

9.2 Specific conditions for safe use models TIF50-F, TIF52-F

Cables, insertions and blind plugs must be suitable for the corresponding Ex classification

as well as for the corresponding operating temperature. Observe the operating instructions

and approvals of the threads and conduit systems used. You must therefore check in the

final application case (e.g. ambient temperature plus 5 K) whether the components used

are suitable. The instruments may not be opened while they are under voltage.

Observe the warnings on the instruments:

"WARNING! – do not open while under voltage"

9. Information on mounting and operation in hazardous areas