Menu guidance of the user interface – WIKA TIF52 Benutzerhandbuch
Seite 25

WIKA operating instructions models TIF50, TIF52
25
GB
14009686.02 03/2012 GB/D
8.2 Main menu "Display"
Function
Factory setting
Unit
Setting the unit for the display of the digital indicator
Here, you can select a unit deviating from the unit of the measuring range of the
connected transmitter. The measured values are then converted automatically
into the deviating unit.
However, only units of the same unit group as the set unit of the measuring range
may be selected.
Setting range (according to unit groups):
- Electrical measurement parameters: V, mA, Ω
- Pressure: bar, mbar, PSI, hPa, kPa, mmH
2
O, mH
2
O, inHG
- Temperature: °C, °F, K
- Others: %, USER
mA
Unit lock
By activating the unit lock, the set display unit is locked to protect the unit against
modifications. The display shows the sign . Modifications of the measuring
range are converted automatically.
The unit lock only functions if the units of the measuring range and the display
originate from the same unit group.
When connecting a transmitter and its configuration via HART
®
with a unit of
another unit group, then the unit lock is deactivated. In this case, the display unit is
set according to the configured measuring range unit.
Setting range:
- not locked (UnLoC)
- locked (LoC)
UnLoC
Indication range format
Setting the decimal point for the indication range of the digital indicator
Setting range: 0 ↔ 0.0 ↔ 0.00 ↔ 0.000 ↔ 0.0000
00.000
Filter
Activation of the digital filter of the 1st order;
Setting range: 0 ... 10
0
Alarm
From this menu item it is possible to branch into the submenu 2 for the alarm
configuration by selecting SELECT.
-----
Min/Max memory
From this menu item it is possible to branch into the submenu 2 for the min./max.
memory by selecting SELECT.
-----
8. Menu guidance of the user interface