Menu guidance of the user interface – WIKA TIF52 Benutzerhandbuch

Seite 27

Advertising
background image

WIKA operating instructions models TIF50, TIF52

27

GB

14009686.02 03/2012 GB/D

8.3 Main menu "Configuration"

Function

Factory setting

Language

Setting the language
Setting range:

- dEU (GEr): German

- EnG: English

EnG

Contrast

Setting range:

1 - 4

2

Reset

A reset is used to reset all settings of the digital indicator to the factory settings.

The SELECT key must be pressed twice to activate the reset.

After pressing the key once, the RESET display starts flashing and after the

second actuation of the key, the display is completely hidden and the reset is

carried out.

-----

USER-unit

The user can freely program a 6-digit user unit.

The 6 characters can be selected from an alphanumeric character set.

By pressing the SELECT key, the first digit is enabled and starts flashing. Use the

arrow keys to select the desired character. By pressing the SELECT key again, the

character is confirmed and the next digit is enabled.

USER

Min. failure message

Setting the current value which releases the min. failure message when this value

is reached or not reached.

The min. failure message is displayed with 5 underscores (_ _ _ _ _) and the

message OUTMIN.
Setting range: 3.5 ... 3.9 mA

3.6

Max. failure message

Setting the current value upon reaching or exceeding of which the max. failure

message is released.

The max. failure message is displayed with 5 upper scores (

_ _ _ _ _

) and the

message OUTMAX.
Setting range: 20.1 ... 21.5 mA

21.0

Firmware version

The number of the firmware version used is displayed.

-----

8. Menu guidance of the user interface

Advertising