WIKA operating instructions model TR30 per ATEX

GB

3. Specifications

3.1 Output signal Pt100, model TR30-P
Measuring element and measuring insert

The Pt100 measuring element is located in the thermometer's probe tip.

Output signal Pt100, model TR30-P

Temperature range

Measuring range without neck tube -50 ... +150 °C, with neck tube -50 ... +250 °C

Measuring element

Pt100 (measuring current: 0.1 ... 1.0 mA)

Connection method

2-wire

3-wire

4-wire

Sensor tolerance value

1)

per DIN EN 60751

Class B

Class A

Electrical connection

Angular DIN connector Form A, M12 x 1 circular connector, 4-pin

Explosion protection

(option)

Intrinsically safe to Ex-i (ATEX) gas/dust, per Directive 94/9/EC

Marking: II 1G Ex ia IIC T* or II 2D Ex iaD 21 T*

Readings in % refer to the measuring span

For a correct determination of the overall measuring error, both sensor and transmitter measuring deviations have to

be considered.

1) For detailed specifications for Pt100 sensors, see Technical Information IN 00.17 at www.wika.com.

3.2 Output signal 4 ... 20 mA, model TR30-W
Measuring element and measuring insert

The Pt100 measuring element is located in the thermometer's probe tip.

The 4 ... 20 mA transmitter is mounted and potted within the tubular body of the

thermometer.

Output signal 4 ... 20 mA, model TR30-W

Temperature range

Measuring range without neck tube -50 ... +150 °C,

with neck tube -50 ... +250 °C

2)

Measuring element

Pt100 (measuring current: 0.5 mA)

Sensor tolerance value

1)

per DIN EN 60751

Class B

Measuring span

minimum 20 K, maximum 300 K

Basic configuration

Measuring range 0 ... 150 °C, other measuring ranges are adjustable

Analogue output

4 ... 20 mA, 2-wire

Measuring error

per DIN EN 60770, 23 °C ±5 K

0.2 % (Transmitter)

3)

Linearisation

linear with temperature per DIN EN 60751

Linearisation error

±0.1 %

4)

Switch-on delay, electrical

< 10 ms

Signalling of sensor burnout

configurable: NAMUR downscale < 3.6 mA (typically 3 mA)

NAMUR upscale > 21.0 mA (typically 23 mA)

Sensor short-circuit

not configurable, generally NAMUR downscale < 3.6 mA (typ. 3 mA)

Load RA

RA ≤ (UB - 9 V) / 0.023 A with RA in Ω and UB in V

Effect of load

± 0.05 % / 100 Ω