11258421.10 08/2014 GB/D

20

WIKA operating instructions model T32.xS

6.3 Configuration

The following parameters can all be configured: sensor model, sensor

connection, user measuring range, output limit, alarm indication,

terminal voltage monitoring, sensor break monitoring, measuring

range monitoring, measuring rate, damping, write protection, offset

values (1-point correction), Tag No. and user linearisation (custom

chararcteristic curve). Furthermore, a linear transformation of the

process value is possible using a 2-point correction.
User linearisation:

Via software, customer-specific sensor characteristics can be stored

in the transmitter in order to define other sensor types. Number of

auxiliary points: min. 2; max. 30. If more than 2 sensors are connected

(dual sensor function) further configurations can be carried out. With

the dual sensor function, two identical sensors (resistance sensor or

thermocouple) with the same measuring range are connected and

then processed together.

The transmitters are delivered with a basic configuration (see data

sheet TE 32.04) or configured according to customer specifications.

If the configuration is changed afterwards, the modifications must be

noted on the label using a water-resistant felt-tip pen.

A simulation of the input value is not required to configure

the T32.

A sensor simulation is only required for the functional test.

6. Commissioning, operation

6.2.2 Transmitter in rail mounting version (model T32.3S)

Fasten the rail mounting case (model T32.3S) onto a 35 mm top-hat

rail (EN 60175) by simply locking it into place without the need for any

tools.

Disassembly is achieved by unlocking the locking element.